Requirement #6

open
MB

REQ-PLATFORM-004: Controlled Overvoltage Operation

Requirement #6: REQ-PLATFORM-004: Controlled Overvoltage Operation

Added by Michelle Bausager about 2 months ago.

Status:
New
Priority:
Normal

Description

Requirement statement

The system shall maintain controlled functional operation for HVDC bus voltages above the defined operating range and up to 900 Vdc for a cumulative duration of up to 60 seconds within any rolling 1-hour period.
If the cumulative duration exceeds 60 seconds within the rolling 1-hour period, the system shall transition to a protective shutdown state.

Rationale

This ensures ride-through capability during transient and temporary fault conditions without unnecessary system shutdown.

Definition

The cumulative duration shall be determined based on continuous monitoring of the HVDC bus voltage.

Notes

The protective shutdown state is not defined here.


Related issues 1 (1 open0 closed)

Related to Requirement #5: REQ-PLATFORM-003: HVDC bus voltage toleranceNewActions