REQ-PLATFORM-004: Controlled Overvoltage Operation
Requirement #6:
REQ-PLATFORM-004: Controlled Overvoltage Operation
Status:
New
Priority:
Normal
Description
Requirement statement¶
The system shall maintain controlled functional operation for HVDC bus voltages above the defined operating range and up to 900 Vdc for a cumulative duration of up to 60 seconds within any rolling 1-hour period.
If the cumulative duration exceeds 60 seconds within the rolling 1-hour period, the system shall transition to a protective shutdown state.
Rationale¶
This ensures ride-through capability during transient and temporary fault conditions without unnecessary system shutdown.
Definition¶
The cumulative duration shall be determined based on continuous monitoring of the HVDC bus voltage.
Notes¶
The protective shutdown state is not defined here.